DUCT CFM · REVIEWED SEPTEMBER 2026 · BY BRENT

DUCT CFM

CFM = BTU ÷ (1.08 × ΔT)
BTU/hr
°F
RESULT
FILL IN ABOVE
CFM = BTU ÷ (1.08 × ΔT). Cooling ΔT ≈ 20°F. Forced-air heating ΔT ≈ 60°F.

Duct CFM chart — airflow by heat load and temperature split

Airflow needed to move a given load, from the sensible heat equation. The 20–25°F columns are cooling, where the split runs between roughly 55°F supply air and 75°F return. The 60–70°F columns are forced-air heating, and they are why the same blower moves far less air in winter: a wider temperature split carries the same energy on less air.

Heat loadTonsΔT 20°FΔT 25°FΔT 60°FΔT 70°F400 CFM/ton rule
6,000 BTU/hr0.502782229379200
9,000 BTU/hr0.75417333139119300
12,000 BTU/hr1.00556444185159400
18,000 BTU/hr1.50833667278238600
24,000 BTU/hr2.001,111889370317800
30,000 BTU/hr2.501,3891,1114633971,000
36,000 BTU/hr3.001,6671,3335564761,200
42,000 BTU/hr3.501,9441,5566485561,400
48,000 BTU/hr4.002,2221,7787416351,600
60,000 BTU/hr5.002,7782,2229267942,000

CFM = BTU/hr ÷ (1.08 × ΔT), the standard-air sensible heat equation used for Manual D duct layout. The last column is the equipment-side 400 CFM per ton rule of thumb.

These are theoretical airflows at zero static pressure. Real duct runs deliver 70–90% of this once friction is counted, and register and trunk sizing come from a Manual D layout off a room-by-room Manual J. Run your own load and split above.

RECOMMENDED TOOLS
HVAC Tools we recommend for projects like this

About this calculator

This duct CFM calculator gives the airflow needed (in cubic feet per minute) to deliver a given heating or cooling load. The sensible heat formula CFM = BTU/hr ÷ (1.08 × ΔT) is what HVAC contractors use for room-by-room duct sizing in a Manual D layout. ΔT is the difference between the supply air temperature and the return air temperature — typically 20°F for cooling and 50–70°F for forced-air heating. The industry rule of thumb is 400 CFM per ton of cooling (1 ton = 12,000 BTU/hr), which lines up with a 20°F cooling ΔT. Duct sizing follows ACCA Manual D — match CFM per room from a Manual J load calc.

How to use this calculator

Enter the heat load in BTU/hr — for cooling, use the room's cooling load (~20 BTU/ft² rule of thumb or your Manual J number). For heating, use the room's heat loss. Set the supply temp differential (ΔT): 20°F for cooling (the standard delta between 55°F supply air and 75°F return), 50–70°F for forced-air heating, or whatever your equipment specs.

The calculator returns the airflow in CFM plus a comparison to the 400 CFM/ton rule of thumb (which is what equipment is rated for at standard cooling conditions). Use the result to size individual room registers and trunk ducts in a Manual D layout.

Worked example

For a 24,000 BTU/hr (2-ton) cooling load with 20°F supply ΔT:

CFM = 24,000 ÷ (1.08 × 20) = 24,000 ÷ 21.6 = 1,111 CFM. Rule of thumb: 2 tons × 400 = 800 CFM (lower because the rule assumes 22-25°F ΔT for proper dehumidification).

For a 60,000 BTU/hr forced-air heating load with 60°F ΔT:

CFM = 60,000 ÷ (1.08 × 60) = 926 CFM. Same blower, but the higher heating ΔT lets you move the same energy with less air than cooling.

For an individual bedroom with 4,000 BTU/hr cooling load: 4,000 ÷ 21.6 = 185 CFM. Two 6×12 supply registers (~95 CFM each at 0.10" w.c. drop) would handle this room.

Common mistakes & waste factors

Using cooling ΔT for heating. Cooling runs ~20°F ΔT; forced-air heating runs 50–70°F ΔT. Same load, different airflow. Mixing them up oversizes ducts by 3×.

Forgetting that 400 CFM/ton is a rule of thumb. Variable-speed equipment can run 350-450 CFM/ton depending on indoor humidity and conditions. The CFM = BTU ÷ (1.08 × ΔT) formula is more accurate for individual room sizing.

Ignoring static pressure. CFM is theoretical airflow at zero static. Real ducts have friction losses; actual CFM is 70-90% of theoretical for well-designed systems.

Sizing only for cooling. In cold climates, the heating CFM might be lower than cooling — but the duct still needs to be sized for the larger of the two loads.

Rules of thumb

CFM = BTU/hr ÷ (1.08 × ΔT). 1.08 = constant for standard air conditions.

Cooling ΔT: 20°F (high humidity climates) to 25°F (dry climates).

Forced-air heating ΔT: 50–70°F (entry-level furnaces 50°F, modulating 70°F).

400 CFM per ton of cooling is the equipment-side rule. Lower CFM/ton dehumidifies more; higher CFM/ton cools faster.

Individual room registers: 6×12 ~95 CFM, 4×10 ~70 CFM, 8×16 ~150 CFM at 0.10" w.c. friction loss.

Common questions

Tool and material links below are affiliate links — we may earn a small commission if you buy, at no extra cost to you.

What is the typical CFM per ton of cooling?
400 CFM per ton is the residential rule of thumb, which lines up with a 20°F supply-vs-return ΔT. High-humidity climates sometimes target 350 CFM/ton for better dehumidification; dry climates may run 450 CFM/ton for sensible-only cooling.
How do I figure CFM for a single room?
Two ways. (1) Run a Manual J load on that room, then apply CFM = BTU ÷ (1.08 × ΔT). (2) Proportional: room CFM = (room load ÷ total load) × system CFM. Method 2 is what most installers do once Manual J gives them the per-room loads.
Why does correct duct sizing matter?
Undersized ducts starve airflow — coils freeze in cooling mode, heat exchangers crack in heating mode, and equipment lifespan drops. Oversized ducts waste fan energy, leak more, and can produce uncomfortable air velocity. Manual D sizing pays back in efficiency and longevity. Verify register CFM with a hot-wire anemometer or airflow capture hood.