VOLTAGE DROP
About this calculator
This voltage drop calculator computes the voltage lost in a copper wire run, which the NEC recommends keeping at or below 3% on branch circuits and 5% combined feeder + branch. Use one-way distance — the calculator doubles it for round-trip. K = 12.9 for copper at 75°C. For aluminum wire, multiply the drop by 1.6.
How to use this calculator
Enter your system voltage (120 for standard outlets/lights, 240 for dryers/AC/EV chargers), the circuit's continuous current draw in amps, and the one-way distance from panel to load in feet (the calculator doubles it for round-trip). Pick the wire size you're planning to use in AWG (American Wire Gauge — lower numbers are thicker wire).
The result is voltage dropped over the run plus drop as a percentage of system voltage. NEC recommends ≤3% drop on branch circuits and ≤5% combined for feeder + branch. The status indicator flags whether your spec passes, is marginal, or needs upsizing. K = 12.9 for copper at 75°C; for aluminum, multiply the result by 1.6.
Worked example
Say you're running a 20A 120V circuit 75 feet to a detached garage on 12 AWG copper:
VD = (2 × 12.9 × 20 × 75) ÷ 6,530 = 38,700 ÷ 6,530 = 5.93 V. Drop %: 5.93 ÷ 120 = 4.94%.
Status: marginal — exceeds NEC's 3% recommendation. Voltage at the load: 120 − 5.93 = 114 V (lights flicker, motors run hot).
Upsize to 10 AWG: VD = (2 × 12.9 × 20 × 75) ÷ 10,380 = 3.73 V = 3.1%. Status: still slightly marginal but acceptable. Upsize to 8 AWG: 2.34 V = 1.95% — clean install.
For a 50A EV charger at 240V over 100 ft on 6 AWG: VD = (2 × 12.9 × 50 × 100) ÷ 26,240 = 4.92 V = 2.05%. Passes comfortably.
Common mistakes & waste factors
Using one-way distance without doubling. The calculator doubles it for you, but if you're doing the math by hand, remember the current flows panel → load → back to panel. A 75-foot run is 150 feet of conductor.
Assuming voltage drop only matters for long runs. A 14 AWG circuit at 15A drops 4.7% over just 50 feet at 120V — already over NEC recommendation. Long runs make it worse, but short undersized runs also fail.
Forgetting that aluminum needs a bigger conductor. Aluminum wire has 1.6× the resistance of copper at the same AWG. A 10 AWG aluminum run drops the same as 12 AWG copper.
Sizing for ampacity but not drop. NEC requires the wire handle the current safely (ampacity), but drop is a separate calculation. A wire that's safe might still cause equipment to malfunction from low voltage. Always check both.
Rules of thumb
NEC: ≤3% drop on branch circuits, ≤5% feeder + branch combined.
Quick mental math: at 120V, a 20A circuit on 12 AWG drops about 1% per 15 ft of one-way run. So 75 ft = ~5% drop. Useful for ballpark sizing.
Copper K = 12.9 (75°C terminations). Aluminum K = 21.2 (multiply copper drop by 1.6 for aluminum at same AWG).
Long runs (100+ ft) almost always need the next-larger wire size beyond ampacity minimum.
For 240V circuits, drop percentage is half of the same circuit at 120V because voltage doubled and current halved for the same load.
Common questions
Tool and material links below are affiliate links — we may earn a small commission if you buy, at no extra cost to you.