VOLTAGE DROP · REVIEWED SEPTEMBER 2026 · BY BRENT

VOLTAGE DROP

VD = 2·K·I·L ÷ CM
V
A
ft
RESULT
FILL IN ABOVE
NEC recommends ≤3% drop on branch circuits, ≤5% total. K = 12.9 for copper.
RECOMMENDED TOOLS
Electrical Tools we recommend for projects like this

About this calculator

VD = 2·K·I·L ÷ CM PANEL V LOAD (I amps) one-way distance L (ft) — current travels 2L AWG (copper) → CM
Electrical circuit showing voltage source, wire run of length L, load, and voltage drop along the conductor

This voltage drop calculator computes the voltage lost in a copper wire run, which the NEC recommends keeping at or below 3% on branch circuits and 5% combined feeder + branch. Use one-way distance — the calculator doubles it for round-trip. K = 12.9 for copper at 75°C. For aluminum wire, multiply the drop by 1.6.

How to use this calculator

Enter your system voltage (120 for standard outlets/lights, 240 for dryers/AC/EV chargers), the circuit's continuous current draw in amps, and the one-way distance from panel to load in feet (the calculator doubles it for round-trip). Pick the wire size you're planning to use in AWG (American Wire Gauge — lower numbers are thicker wire).

The result is voltage dropped over the run plus drop as a percentage of system voltage. NEC recommends ≤3% drop on branch circuits and ≤5% combined for feeder + branch. The status indicator flags whether your spec passes, is marginal, or needs upsizing. K = 12.9 for copper at 75°C; for aluminum, multiply the result by 1.6.

Worked example

Say you're running a 20A 120V circuit 75 feet to a detached garage on 12 AWG copper:

VD = (2 × 12.9 × 20 × 75) ÷ 6,530 = 38,700 ÷ 6,530 = 5.93 V. Drop %: 5.93 ÷ 120 = 4.94%.

Status: marginal — exceeds NEC's 3% recommendation. Voltage at the load: 120 − 5.93 = 114 V (lights flicker, motors run hot).

Upsize to 10 AWG: VD = (2 × 12.9 × 20 × 75) ÷ 10,380 = 3.73 V = 3.1%. Status: still slightly marginal but acceptable. Upsize to 8 AWG: 2.34 V = 1.95% — clean install.

For a 50A EV charger at 240V over 100 ft on 6 AWG: VD = (2 × 12.9 × 50 × 100) ÷ 26,240 = 4.92 V = 2.05%. Passes comfortably.

Common mistakes & waste factors

Using one-way distance without doubling. The calculator doubles it for you, but if you're doing the math by hand, remember the current flows panel → load → back to panel. A 75-foot run is 150 feet of conductor.

Assuming voltage drop only matters for long runs. A 14 AWG circuit at 15A drops 4.7% over just 50 feet at 120V — already over NEC recommendation. Long runs make it worse, but short undersized runs also fail.

Forgetting that aluminum needs a bigger conductor. Aluminum wire has 1.6× the resistance of copper at the same AWG. A 10 AWG aluminum run drops the same as 12 AWG copper.

Sizing for ampacity but not drop. NEC requires the wire handle the current safely (ampacity), but drop is a separate calculation. A wire that's safe might still cause equipment to malfunction from low voltage. Always check both.

Rules of thumb

NEC: ≤3% drop on branch circuits, ≤5% feeder + branch combined.

Quick mental math: at 120V, a 20A circuit on 12 AWG drops about 1% per 15 ft of one-way run. So 75 ft = ~5% drop. Useful for ballpark sizing.

Copper K = 12.9 (75°C terminations). Aluminum K = 21.2 (multiply copper drop by 1.6 for aluminum at same AWG).

Long runs (100+ ft) almost always need the next-larger wire size beyond ampacity minimum.

For 240V circuits carrying the same load, drop percentage is a QUARTER of the 120V case, not half — the current halves so the volts dropped halve, and the voltage you divide by doubles.

Common questions

Tool and material links below are affiliate links — we may earn a small commission if you buy, at no extra cost to you.

What's an acceptable voltage drop?
NEC recommends max 3% on branch circuits and max 5% combined feeder + branch. Code is a recommendation, not a hard requirement, but exceeding it causes lights to dim, motors to run hot, and electronics to misbehave.
When do I need to upsize wire for distance?
A 15A circuit on 14 AWG copper exceeds 3% drop past about 50 ft (one-way). Past 50 ft, jump to 12 AWG. Past 100 ft, jump to 10 AWG. Long subpanel runs commonly need 8 or 6 AWG even at low amperage.
Does aluminum wire have more voltage drop?
Yes — aluminum has about 1.6× the resistance of same-gauge copper. SE-rated aluminum wire is sized larger to compensate. For a given amperage, aluminum service entrance cable is typically 2 sizes larger (e.g., 4/0 AL replaces 2/0 CU). For verifying drop in the field, a Klein clamp meter reads voltage under load — far more useful than a multimeter at no load.