BREAKER SIZE · REVIEWED MAY 2026 · BY BRENT

CIRCUIT BREAKER SIZE

breaker = next std ≥ load × (1.25 if continuous)
V
RESULT
FILL IN ABOVE
NEC 240.6 standard sizes + 210.20(A) 125% continuous multiplier. Motor circuits flagged for 430.52 sizing. Estimate only — verify with a licensed electrician and local code/inspector before purchase or installation. Not a substitute for engineered drawings.
RECOMMENDED TOOLS
Electrical Tools we recommend for projects like this

About this calculator

This circuit breaker calculator picks the next standard breaker size (NEC 240.6) for a given load. Enter wattage or amperage and the calculator converts watts to amps using your system voltage, applies the NEC 210.20(A) 125% multiplier when the load is continuous (anything operating ≥3 hours — lighting, EV chargers, electric heat), and rounds up to the nearest standard breaker (15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 A). Motor loads use NEC 430.52 sizing (250% inverse-time breaker for typical service factor 1.15 motors) and are flagged separately. ESTIMATE ONLY — final breaker selection must be verified by a licensed electrician and the local AHJ before any work goes in.

How to use this calculator

Pick whether you're entering the load as amps or watts. If watts, set the system voltage so the calculator can convert (120V for standard outlets, 240V for dryers/AC/EV chargers). Pick the load type: continuous (≥3 hr operation like lighting, EV chargers, electric heat) triggers the NEC 210.20(A) 125% multiplier; motor loads use NEC 430.52 with a 250% inverse-time breaker rating.

The calculator returns the next standard breaker size from NEC 240.6 (15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 A) plus a minimum copper wire AWG hint. Match wire size to the breaker; never install a breaker larger than the wire it protects.

Worked example

For a 1,500W microwave on a 120V circuit, non-continuous use:

Base amps: 1,500 ÷ 120 = 12.5 A. Multiplier: 1.0 (non-continuous). Design amps: 12.5 A. Next standard breaker: 15 A.

Min wire: 14 AWG copper. Wired correctly with a 14 AWG home run from the panel and a 15A breaker.

For a 7.7 kW EV charger (32A continuous at 240V):

Base amps: 32. Continuous multiplier: 1.25. Design amps: 40. Next standard breaker: 40 A. Min wire: 8 AWG copper.

For a 5 HP motor on 240V (about 28 A running):

Base: 28 A. Motor multiplier (NEC 430.52): 2.5×. Design: 70 A. Next standard breaker: 70 A. The motor itself is protected by a separate overload device — the breaker only handles short-circuit protection (which is why the inverse-time multiplier is so high).

Common mistakes & waste factors

Forgetting the 125% continuous-load factor. NEC 210.20(A) requires it for any load running 3+ hours. Skipping it means the breaker trips during normal operation.

Matching wire to load instead of to breaker. The breaker protects the wire — wire size must match breaker rating, not just the load. A 12 AWG wire on a 30A breaker is a fire hazard.

Using motor sizing for non-motor loads. The 250% inverse-time multiplier is for motor short-circuit protection only. Applying it to general loads gives wildly oversized breakers.

Ignoring AFCI/GFCI requirements. Some circuits (bedrooms, kitchens, baths, outdoor) require AFCI or GFCI breakers per NEC 210.12 / 210.8. Those breakers cost 3–5× more and have specific compatibility requirements.

Rules of thumb

NEC 240.6 standard sizes: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 A.

Wire to breaker (75°C copper): 14 AWG → 15A. 12 AWG → 20A. 10 AWG → 30A. 8 AWG → 40-50A. 6 AWG → 60-65A.

Continuous load (≥3 hr): multiply amps by 1.25 before sizing.

Motor circuits: NEC 430.52 inverse-time breaker at ~250% of running amps for short-circuit protection (separate overload device handles thermal).

Always match breaker to wire size, never to load alone. Oversized breaker on undersized wire = fire risk.

Common questions

How are standard breaker sizes set?
NEC 240.6(A) lists the standard sizes: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 A and up. Anything else is non-standard and rarely stocked. The calculator always rounds up to the next standard size.
What is the 80% / 125% rule?
Two ways to say the same thing: a continuous load (≥3 hr operation) can be no more than 80% of breaker rating, OR breaker must be sized to 125% of the continuous load. NEC 210.20(A). A 16 A continuous EV charger needs a 20 A breaker; a 20 A non-continuous appliance also lands on a 20 A breaker.
Why are motor breakers oversized?
NEC 430.52 lets motor inverse-time breakers run up to 250% of full-load current to ride out the inrush at startup without nuisance tripping. The motor itself is protected by the overload relay, not the breaker. This is why a 12 A motor can be on a 30 A breaker and still be code-compliant.