BREAKER SIZE · REVIEWED SEPTEMBER 2026 · BY BRENT

CIRCUIT BREAKER SIZE

breaker = next std ≥ load × (1.25 if continuous)
V
RESULT
FILL IN ABOVE
NEC 240.6 standard sizes + 210.20(A) 125% continuous multiplier. Motor circuits flagged for 430.52 sizing. Estimate only — verify with a licensed electrician and local code/inspector before purchase or installation. Not a substitute for engineered drawings.

Breaker size chart — standard sizes and the load each one covers

The standard breaker sizes, and the largest load each one may protect under the three rules the calculator applies. A continuous load — anything running three hours or more, so lighting, electric heat and EV charging — is sized at 125%, which is why a 32 A charger needs a 40 A breaker rather than a 35. Motors use the 250% inverse-time rule instead, because there the breaker only handles short-circuit protection while a separate overload device covers the thermal side.

BreakerMax non-continuous loadMax continuous loadMax motor full-load amps
15 A15 A12 A6 A
20 A20 A16 A8 A
25 A25 A20 A10 A
30 A30 A24 A12 A
35 A35 A28 A14 A
40 A40 A32 A16 A
45 A45 A36 A18 A
50 A50 A40 A20 A
60 A60 A48 A24 A
70 A70 A56 A28 A
80 A80 A64 A32 A
90 A90 A72 A36 A
100 A100 A80 A40 A
110 A110 A88 A44 A
125 A125 A100 A50 A
150 A150 A120 A60 A
175 A175 A140 A70 A
200 A200 A160 A80 A
225 A225 A180 A90 A
250 A250 A200 A100 A

Standard sizes per NEC 240.6(A), residential through light commercial. Continuous-load multiplier per NEC 210.20(A); motor inverse-time multiplier per NEC 430.52.

The breaker protects the conductor, not the load — pairing it with an undersized wire is the dangerous mistake. Size the wire on the wire gauge calculator, and check whether the circuit also needs AFCI or GFCI protection.

RECOMMENDED TOOLS
Electrical Tools we recommend for projects like this

About this calculator

This circuit breaker calculator picks the next standard breaker size (NEC 240.6) for a given load. Enter wattage or amperage and the calculator converts watts to amps using your system voltage, applies the NEC 210.20(A) 125% multiplier when the load is continuous (anything operating ≥3 hours — lighting, EV chargers, electric heat), and rounds up to the nearest standard breaker (15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 A). Motor loads use NEC 430.52 sizing (250% inverse-time breaker for typical service factor 1.15 motors) and are flagged separately. ESTIMATE ONLY — final breaker selection must be verified by a licensed electrician and the local AHJ before any work goes in.

How to use this calculator

Pick whether you're entering the load as amps or watts. If watts, set the system voltage so the calculator can convert (120V for standard outlets, 240V for dryers/AC/EV chargers). Pick the load type: continuous (≥3 hr operation like lighting, EV chargers, electric heat) triggers the NEC 210.20(A) 125% multiplier; motor loads use NEC 430.52 with a 250% inverse-time breaker rating.

The calculator returns the next standard breaker size from NEC 240.6 (15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 A) plus a minimum copper wire AWG hint. Match wire size to the breaker; never install a breaker larger than the wire it protects.

Worked example

For a 1,500W microwave on a 120V circuit, non-continuous use:

Base amps: 1,500 ÷ 120 = 12.5 A. Multiplier: 1.0 (non-continuous). Design amps: 12.5 A. Next standard breaker: 15 A.

Min wire: 14 AWG copper. Wired correctly with a 14 AWG home run from the panel and a 15A breaker.

For a 7.7 kW EV charger (32A continuous at 240V):

Base amps: 32. Continuous multiplier: 1.25. Design amps: 40. Next standard breaker: 40 A. Min wire: 8 AWG copper.

For a 5 HP motor on 240V (about 28 A running):

Base: 28 A. Motor multiplier (NEC 430.52): 2.5×. Design: 70 A. Next standard breaker: 70 A. The motor itself is protected by a separate overload device — the breaker only handles short-circuit protection (which is why the inverse-time multiplier is so high).

Common mistakes & waste factors

Forgetting the 125% continuous-load factor. NEC 210.20(A) requires it for any load running 3+ hours. Skipping it means the breaker trips during normal operation.

Matching wire to load instead of to breaker. The breaker protects the wire — wire size must match breaker rating, not just the load. A 12 AWG wire on a 30A breaker is a fire hazard.

Using motor sizing for non-motor loads. The 250% inverse-time multiplier is for motor short-circuit protection only. Applying it to general loads gives wildly oversized breakers.

Ignoring AFCI/GFCI requirements. Some circuits (bedrooms, kitchens, baths, outdoor) require AFCI or GFCI breakers per NEC 210.12 / 210.8. Those breakers cost 3–5× more and have specific compatibility requirements.

Rules of thumb

NEC 240.6 standard sizes: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 A.

Wire to breaker (75°C copper): 14 AWG → 15A. 12 AWG → 20A. 10 AWG → 30A. 8 AWG → 40-50A. 6 AWG → 60-65A.

Continuous load (≥3 hr): multiply amps by 1.25 before sizing.

Motor circuits: NEC 430.52 inverse-time breaker at ~250% of running amps for short-circuit protection (separate overload device handles thermal).

Always match breaker to wire size, never to load alone. Oversized breaker on undersized wire = fire risk.

Common questions

How are standard breaker sizes set?
NEC 240.6(A) lists the standard sizes: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 A and up. Anything else is non-standard and rarely stocked. The calculator always rounds up to the next standard size.
What is the 80% / 125% rule?
Two ways to say the same thing: a continuous load (≥3 hr operation) can be no more than 80% of breaker rating, OR breaker must be sized to 125% of the continuous load. NEC 210.20(A). A 16 A continuous EV charger needs a 20 A breaker; a 20 A non-continuous appliance also lands on a 20 A breaker.
Why are motor breakers oversized?
NEC 430.52 lets motor inverse-time breakers run up to 250% of full-load current to ride out the inrush at startup without nuisance tripping. The motor itself is protected by the overload relay, not the breaker. This is why a 12 A motor can be on a 30 A breaker and still be code-compliant.