WIRE GAUGE (AWG) · REVIEWED SEPTEMBER 2026 · BY BRENT

WIRE GAUGE (AWG)

AWG = f(amps, NEC 310.16 75°C)
A
V
ft
RESULT
FILL IN ABOVE
NEC 310.16 75°C ampacity + 3% voltage-drop bump. Continuous loads (≥3 hr) require 125% derate — apply manually before entering amps. Estimate only — verify with a licensed electrician and local code/inspector before purchase or installation. Not a substitute for engineered drawings.

Wire size chart — amps to AWG at 75°C

The largest load each conductor size may carry on a 75°C termination, which is what residential and light-commercial breakers, lugs and panelboards are rated for. Aluminum carries roughly 80% of copper at the same gauge, so an aluminum feeder is usually one size larger than the copper it replaces. These are ampacity ceilings only — a long run still has to pass the voltage-drop check.

ConductorCopperAluminumCircular mils
14 AWG15 A4,110
12 AWG20 A15 A6,530
10 AWG30 A25 A10,380
8 AWG50 A40 A16,510
6 AWG65 A50 A26,240
4 AWG85 A65 A41,740
2 AWG115 A90 A66,360
1/0 AWG150 A120 A105,600
2/0 AWG175 A135 A133,100
3/0 AWG200 A155 A167,800
4/0 AWG180 A211,600

NEC Table 310.16, 75°C column, with the NEC 240.4(D) small-conductor limits governing 14, 12 and 10 AWG copper and 12 and 10 AWG aluminum. A dash means the calculator does not tabulate that size in that metal.

Ampacity keeps the conductor from overheating; it says nothing about voltage drop, which is what actually bumps the size on a long run. Enter your run length above to see whether the 3% limit moves you up a gauge.

RECOMMENDED TOOLS
Electrical Tools we recommend for projects like this

About this calculator

This wire gauge calculator returns the minimum AWG (American Wire Gauge) for a copper or aluminum conductor based on circuit amperage and run length. Sizing comes from NEC Table 310.16 at 75°C terminations (the standard for residential and commercial breakers, lugs, and panelboards). The calculator also runs a 3% voltage-drop check on the chosen size and bumps up if a long run pushes drop past code-recommended limits, since NEC 210.19(A) Informational Note 4 caps branch circuits at 3%. ESTIMATE ONLY — final wire size and install must be verified by a licensed electrician and the local AHJ before any work goes in.

How to use this calculator

Enter the circuit's current load in amps. Apply the 125% continuous-load factor first if applicable: dryers, EV chargers, electric heat, and any load running ≥3 hours need amps × 1.25 entered (e.g., 12A continuous → enter 15). System voltage is 120V for standard outlets and lights, 240V for dryers and AC, 208V for commercial 3-phase. One-way run length is the panel-to-load distance.

Pick copper (the common residential default) or aluminum (used for service entrance and large feeders to save cost on heavy gauges). The calculator returns the minimum AWG per NEC 310.16 ampacity tables, then runs a 3% voltage-drop check and bumps up to the next size if the run is too long for the picked gauge.

Worked example

For a 20A 240V circuit running 100 ft on copper:

NEC 310.16 ampacity: 12 AWG copper handles 20A → start at 12 AWG. Voltage-drop check: VD = (2 × 12.9 × 20 × 100) ÷ 6,530 ÷ 240 × 100 = 3.29% — over the 3% cap.

Bumped to 10 AWG: VD = (2 × 12.9 × 20 × 100) ÷ 10,380 ÷ 240 × 100 = 2.07% — passes. Final spec: 10 AWG copper (one size larger than ampacity-only would dictate), 20A breaker.

For a 50A EV charger 80 ft from the panel on copper: 8 AWG handles 50A ampacity. Drop check: 2.60% at 240V — passes without a bump. Final: 8 AWG copper, 50A breaker.

For a 200A service feeder 50 ft to a sub-panel on aluminum: 4/0 aluminum at 200A, drop ~1.2% — passes. Saves significant material cost vs 3/0 copper.

Common mistakes & waste factors

Forgetting the 125% continuous-load factor. NEC requires sizing wire and breaker for continuous loads (≥3 hr) at 125% of rated load. A 32A EV charger running for hours needs to be sized as if it's 40A.

Using residential 60°C terminations on commercial gear. Most modern panelboards have 75°C terminations (the calculator assumes this). Older or budget gear with 60°C terminations needs a larger wire for the same amperage.

Sizing for ampacity but not drop. Ampacity keeps the wire from melting; voltage drop keeps motors and lights running properly. Long runs almost always need the next size up beyond ampacity minimum.

Mixing aluminum and copper at terminations. Aluminum-to-copper junctions need anti-oxidant compound and listed connectors (CO/ALR or AL-CU rated). Otherwise corrosion creates resistive joints that overheat and burn.

Rules of thumb

Copper, 75°C column of NEC 310.16 with the 240.4(D) small-conductor caps applied: 14 AWG = 15A · 12 = 20A · 10 = 30A · 8 = 50A · 6 = 65A · 4 = 85A · 2 = 115A · 1/0 = 150A.

Aluminum runs at about 80% of copper ampacity for the same AWG — usually needs the next size larger.

Continuous loads (≥3 hr): apply ×1.25 to amps before sizing.

Voltage drop bump: roughly add one wire size for every 50–100 ft beyond what ampacity dictates.

Service entrance: 4/0 aluminum or 2/0 copper handles 200A. Common residential service today.

Common questions

Tool and material links below are affiliate links — we may earn a small commission if you buy, at no extra cost to you.

What AWG is needed for 20 amps?
12 AWG copper handles 20 A at 75°C terminations per NEC 310.16. 14 AWG is rated 15 A and pairs with a 15 A breaker only. Aluminum runs one size larger — 10 AWG aluminum is the minimum for a 20 A circuit. A pair of Klein wire strippers sized for 10-22 AWG handles every common residential gauge in one tool.
When does run length force me to upsize?
Voltage drop bumps wire size when the round-trip drop exceeds 3% (NEC 210.19(A) Informational Note 4). On 12 AWG copper at 20 A and 120 V, that hits at roughly 46 ft one-way — at 16 A continuous it is about 57 ft. On 240 V circuits carrying the same load the percentage drops to a quarter, so the permitted length is far greater. Detached buildings, well pumps, and EV chargers are the usual offenders.
Do I need to derate for continuous loads?
Yes. NEC 210.19(A)(1) and 215.2 require conductor and breaker to be sized at 125% of continuous load (anything operating 3 hours or longer — EV chargers, electric heat, sign lighting). Multiply the actual load by 1.25 before entering it in the calculator.